Surge Protection Devices for protecting low voltage equipment against lightning and surge damages AC and DC Applications.
1,2,3,4 -pole lightning and surge arresters, Iimp = 7 kA/pole. Max. continuous operating voltage 275 V AC, Max. discharge current 50 kA
• for protecting low voltage equipment against lightning and surge damages
• for installation in conformity with the lightning protection zones concept at LPZ 0-1
• designed according to IEC 61643-11:2011
Max. continuous operating voltage Uc | 275 V AC |
Nom. discharge current (8/20 μs) In | 20 kA |
Max. discharge current (8/20 μs) Imax | 50 kA |
Impulse discharge current (10/350 μs) Iimp | 7 kA |
Voltage protection level Up | ≤ 1,5 kV |
Response time ta | ≤ 100 ms |
TOV withstand (5 s) Ut | 355 V |
Index | Product | Number of poles |
2617125 | RSP-T1T2-AC 7/1P | 1 pole |
2617126 | RSP-T1T2-AC 7/2P | 2 poles |
2617127 | RSP-T1T2-AC 7/3P | 3 poles |
2617128 | RSP-T1T2-AC 7/4P | 4 poles |
2617129 | RSP-T1T2-AC 7/1+NPE | 2 poles (1+NPE) |
2617130 | RSP-T1T2-AC 7/3+NPE | 4 poles (3+NPE) |
1,2,3,4 -pole lightning and surge arresters limp = 12,5 kA/ pole. Max. continuous operating voltage 275 V AC, Max. discharge current 60 kA
• for protecting low voltage equipment against lightning and surge damages
• for installation in conformity with the lightning protection zones concept at LPZ 0-1
• designed according to IEC 61643-11:2011
Max. continuous operating voltage Uc | 275 V AC |
Nom. discharge current (8/20 μs) In | 30 kA |
Max. discharge current (8/20 μs) Imax | 60 kA |
Impulse discharge current (10/350 μs) Iimp | 12,5 kA |
Voltage protection level Up | ≤ 2 kV |
Response time ta | ≤ 100 ms |
TOV withstand (5 s) Ut | 355 V |
Index | Product | Number of poles |
2617119 | RSP-T1T2-AC 12.5/1P | 1 pole |
2617120 | RSP-T1T2-AC 12.5/2P | 2 poles |
2617121 | RSP-T1T2-AC 12.5/3P | 3 poles |
2617122 | RSP-T1T2-AC 12.5/4P | 4 poles |
2617123 | RSP-T1T2-AC 12.5/1P +NPE | 2 poles (1+NPE) |
2617124 | RSP-T1T2-AC 12.5/3+NPE | 4 poles (3+NPE) |
1,2,3,4 -pole lightning and surge arresters, Imax = 40 kA/ pole. Max. continuous operating voltage 275 V AC. Nom. discharge current 10 kA
• for protecting low voltage equipment against lightning and surge damages
• for installation in conformity with the lightning protection zones concept at LPZ 0-1
• designed according to IEC 61643-11:2011
Max. continuous operating voltage Uc | 275 V AC |
Nom. discharge current (8/20 μs) In | 20 kA |
Max. discharge current (8/20 μs) Imax | 40 kA |
Voltage protection level Up | ≤ 1,5 kV |
Response time ta | ≤ 25 ms |
Max. backup fuse | 355 V |
Index | Product | Number of poles |
2617131 | RSP-T2-AC/1P | 1 pole |
2617132 | RSP-T2-AC/2P | 2 poles |
2617133 | RSP-T2-AC/3P | 3 poles |
2617134 | RSP-T2-AC/4P | 4 poles |
2617135 | RSP-T2-AC/1P+NPE | 2 poles (1+NPE) |
2617136 | RSP-T2-AC/3P+NPE | 4 poles (3+NPE) |
Max. discharge current: 50 kA. Category IEC / EN / VDE: class I+II, II / type 1+2, 2 / B+C, C. Protection methods: (+)-PE, (-)-PE, (+)-(-). Protective elements: MOV. Enclosure: modular.
• For the protection of low-voltage devices against lightning strikes and surges,
• For installation according to the lightning protection zone (LPZ) concept in LPZ 0-1,
• Designed in accordance with the IEC 61643-31:2018 standard.
• Surge protection devices protect against lightning-induced surges in solar systems (photovoltaic power systems),
• These units must be installed in parallel in DC networks that need to be protected and provide both common and differential protection modes,
• Their location is recommended at both ends of the DC power line (on the solar panel side and the inverter/transformer side), especially if the line is external and long.
• RSP-T…-DC…/… is an SPD of class I+II, II for low-voltage power systems,
• Primarily installed in the main distribution cabinet,
• The surge protectors are equipped with high-energy MOV (metal oxide varistors) with special thermal disconnectors and associated fault indicators.
RSP-T1T2 -DC 9/3P | RSP-T1T2 -DC 6.25/3P | |
Maximum continuous operating voltage Uc | 1000 V DC | |
Nominal discharge current (8/20 μs) In | 20 kA | |
Maximum discharge current (8/20 μs) Imax | 50 kA | |
Peak current (10/350 μs) Iimp | 9 kA | 6,25 kA |
Protection level Up | 4,5 kV | |
Response time | ≤ 100 ns | |
Ambient temperature (operation) | -40…+80 °C (parallel connection) / -40…+60 °C (through connection) | |
Cross-sectional area of wires connected to terminals | 35 mm² (solid) / 50 mm² (stranded) |
Index | Commercial code | Number of poles |
2617144 | RSP-T1T2 -DC 9/3P | 3-pole |
2617145 | RSP-T1T2 -DC 6.25/3P | 3-pole |
Max. discharge current: 40 kA. Category IEC / EN / VDE: class I+II, II / type 1+2, 2 / B+C, C. Protection methods: (+)-PE, (-)-PE, (+)-(-). Protective elements: MOV. Enclosure: modular.
• For the protection of low-voltage devices against lightning strikes and surges,
• For installation according to the lightning protection zone (LPZ) concept in LPZ 0-1,
• Designed in accordance with the IEC 61643-31:2018 standard.
• Surge protection devices protect against lightning-induced surges in solar systems (photovoltaic power systems),
• These units must be installed in parallel in DC networks that need to be protected and provide both common and differential protection modes,
• Their location is recommended at both ends of the DC power line (on the solar panel side and the inverter/transformer side), especially if the line is external and long.
• RSP-T…-DC…/… is an SPD of class I+II, II for low-voltage power systems,
• Primarily installed in the main distribution cabinet,
• The surge protectors are equipped with high-energy MOV (metal oxide varistors) with special thermal disconnectors and associated fault indicators.
RSP-T2 -DC/2P | ||
Maximum continuous operating voltage Uc | 1000 V DC | |
Nominal discharge current (8/20 μs) In | 20 kA | |
Maximum discharge current (8/20 μs) Imax | 40 kA | |
Protection level Up | 4 kV | |
Response time | ≤ 25 ns | |
Ambient temperature (operation) | -40…+80 °C | |
Cross-sectional area of wires connected to terminals | 1,5…25 mm² (solid) / 35 mm² (stranded) |
Index | Commercial code | Number of poles |
2617146 | RSP-T2 -DC/2P | 2-pole |
2617147 | RSP-T2 -DC/3P | 3-pole |